CalderaSpas Moorea Owner's Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
10
ELECTRICAL INSTALLATION
ELECTRICAL REQUIREMENTS AND PRECAUTIONS
Your Caldera
®
Spa has been carefully designed to give you maximum safety against electrical shock. Connecting the spa to an improperly wired circuit will negate
many of the spa’s safety features. Improper wiring may also cause electrocution, risk of fire, and other risks of injuries. Please read and follow the electrical installation
requirements and instructions for your spa completely!
230 VOLT PERMANENTLY CONNECTED
CALDERA SPAS MUST BE WIRED IN ACCORDANCE WITH ALL APPLICABLE LOCAL ELECTRICAL CODES. ALL ELECTRICAL WORK SHOULD BE DONE BY AN
EXPERIENCED LICENSED ELECTRICIAN. WE RECOMMEND THE USE OF APPROPRIATE ELECTRICAL CONDUIT, FITTINGS, AND WIRE FOR ALL CIRCUITS.
An electrical subpanel containing two GFCI breakers is included with each spa. We recommend that this subpanel be used to supply power and protect the spa.
This subpanel requires a 50 amp, single phase, 230 volt, four wire service (two line, one neutral, one ground). The ground wire must never be less than #10 AWG. Use
NEC 250-122 (table) and local codes for more information. A minimum #10 AWG solid copper bond wire is also required.
Mount the subpanel in the vicinity of the spa, but not within five feet, in accordance with local codes.
INSTALLATION INSTRUCTIONS
\To connect the electrical service, first remove the screws from the equipment compartment door, lower the door one inch and remove the door.
Locate the spa control box. Remove the screws on the front of the control box and remove the control box cover.1.
Route the electrical service from the subpanel into the spa equipment compartment. 2.
NOTE: The subpanel must be placed in sight of the spa, no closer than five feet.
Connect wire to bottom of control box using a minimum of 3.
c
/v” liquid-tight, flex conduit fitting.
WIRING CONNECTIONS
Identify the TB-1 terminal block, located inside the control box at the lower left-hand corner.1.
Connect the #12 AWG, BLUE wire, from the subpanel 20 amp breaker, terminal L1 to TB-1, terminal 12.
Connect the #12 AWG, RED wire, from the subpanel 20 amp breaker, terminal L2 to TB-1, terminal 33.
NOTE: The WHITE neutral wire must be attached to the LOAD neutral on the 230 volt, 30 amp breaker (not to the neutral bus bar in the subpanel). The WHITE
neutral wire coming from the breaker itself is already connected to the neutral bus bar.
Connect the #10 AWG, BLUE wire, from the subpanel 30 amp breaker, terminal L1 to TB-1, terminal 24.
Connect the #10 AWG, RED wire, from the subpanel 30 amp breaker, terminal L2 to TB-1, terminal 45.
Connect the #10 AWG, WHITE wire, from the subpanel 30 amp breaker, terminal N (load neutral) to TB-1, terminal 56.
Connect the #10 AWG, GREEN wire, from the subpanel GROUND bar to TB-1, system ground terminal.7.
Using the pressure wire connector provided on the outside of the control box, bond the spa to all exposed metal equipment or fixtures, handrails, and the concrete 8.
pad (if applicable) per N.E.C. and local codes.
Replace the control box cover and securely tighten the fastening screws. Close and secure the equipment compartment door as follows:9.
Place top of door or panel directly below bartop against the frame of the spa.•
Push bottom of door or panel against the spa frame.•
Slide door or panel upward (pushing in on center of door) until screw holes line up.•
Slightly pull on door or panel, if door remains against the spa then replace the screws.•
If the door does not lock into position, repeat the previous steps.•
WARNING: FILL THE SPA WITH WATER BEFORE TURNING ON THE POWER! (See STARTUP AND REFILL PROCEDURES.)
Once your spa has been filled with water, turn it on and test all of the circuit breakers.
NOTE: If both breakers immediately trip, verify that the #10 AWG WHITE neutral wire is connected from TB-1 terminal 5 to the N (load neutral) terminal of the 30 amp
subpanel breaker. Each breaker should be tested prior to each use. Here’s how:
Push the “TEST” button on each GFCI breaker, and observe it click OFF.1.
Wait 30 seconds, then push the breaker switch to the OFF (down) position (to ensure that it has completely disengaged), then push the breaker switch to the ON 2.
(up) position. If you don't wait 30 seconds, the spa’s control panel may flash four lines on and off – try again.
If any of the GFCI breakers fails to operate in this manner, your spa may have an electrical malfunction, and you may be at risk of electrical shock. Turn off all circuits and
do not use the spa until the problem has been corrected by an authorized service agent.
SERVICE NOTE: All Caldera spas have diagnostic functions that are displayed on the control panel. The control panel will display four flashing lines if the heater high
limit thermostat has tripped. If the four flashing lines are visible, follow the instructions in the troubleshooting section to identify and correct the cause. The four flashing
lines will stop flashing once the problem has been corrected.
WARNING: Removing or bypassing any GFCI breaker will result in an unsafe spa and will void the spa’s warranty.
IMPORTANT: If you ever need to move or relocate your Caldera spa, it is essential that you understand and apply these installation requirements. Your Caldera spa has
been carefully engineered to provide maximum safety against electric shock. Remember, connecting the spa to an improperly wired circuit will negate many of its safety
features.
NOTE: Long wiring runs may require larger-gauge wire than stated.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 43 44

Comments to this Manuals

No comments